Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
12 4 7 1200
6 7 1200
8 7 1200
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
36.8 29.3 7.7 1.5 0.609 1.1 1.9
51.2 35.8 10.8 3.6 0.962 1.5 2.6
60.5 40.3 12.7 5.3 1.312 1.8 3.1
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
25.7 25.7 5.5 0.8 0.467 0.8 1.3
37.1 30.6 7.8 1.9 0.882 1.1 1.9
44.7 33.9 9.5 3.5 1.228 1.4 2.3


DIMENSIONS - HORIZONTAL AIR HANDLER 800 THRU 2000 CFM
Model BWH
A
B
C
D
E
F
G
H J K L M N Filter Size
12
30 1/8
39 1/8
20 1/2
11 11/16
13 1/2
17 1/2
20
8 5/16 23 6 5/8 1 28 1/8 32 (1) 20x25x2

ModelBWHB& BXHB-08 thru 20 / BWHD &BXHD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.