Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
16 4 7 1600
6 7 1600
8 7 1600
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
55.5 41.6 11.7 3.0 0.584 1.7 2.8
74.0 50.2 15.7 7.0 0.910 2.2 3.8
85.3 55.8 18.0 11.7 1.232 2.6 4.4
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
40.2 35.6 8.5 2.0 0.526 1.2 2.1
53.9 42.6 11.4 3.9 0.841 1.6 2.8
63.3 46.5 13.3 6.7 1.159 1.9 3.2


DIMENSIONS - HORIZONTAL AIR HANDLER 800 THRU 2000 CFM
Model BWH
A
B
C
D
E
F
G
H J K L M N Filter Size
16
38 1/16
39 1/8
20 1/2
11 11/16
13 1/2
17 1/2
20
12 1/4 29 5/8 6 5/8 1 3/8 36 1/16 40 (1) 16x20x2

ModelBWHB& BXHB-08 thru 20 / BWHD &BXHD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.