Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
8 4 3 800
6 7 800
8 7 800
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
28.7 21.3 6.0 5.8 0.590 2.0 3.4
31.5 22.8 6.6 1.3 0.872 0.9 1.6
38.3 25.9 8.1 2.3 1.199 1.2 2.0
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
20.8 18.3 4.4 3.6 0.533 1.5 2.5
22.8 19.6 4.8 1.1 0.795 0.7 1.2
27.9 21.7 5.9 1.3 1.114 0.8 1.4


DIMENSIONS - VERTICAL AIR HANDLER 800 THRU 3000 CFM FOR MODELS BBVW, BBVX
Model BWV
A
B
C
D
E
F
G
H J K L M N Filter Size
08
24 1/16
27 1/8
46
14
20
17 1/2
20
2 1/32 18 11 1/8 1 26 20 1/8 (1) 20x20x2

ModelBWVB& BXVB-08 thru 20 / BWVD & BXVD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.