Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
12 4 7 1200
6 7 1200
8 7 1200
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
36.8 29.3 7.7 1.5 0.609 1.1 1.9
51.2 35.8 10.8 3.6 0.962 1.5 2.6
60.5 40.3 12.7 5.3 1.312 1.8 3.1
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
25.7 25.7 5.5 0.8 0.467 0.8 1.3
37.1 30.6 7.8 1.9 0.882 1.1 1.9
44.7 33.9 9.5 3.5 1.228 1.4 2.3


DIMENSIONS - VERTICAL AIR HANDLER 800 THRU 3000 CFM FOR MODELS BBVW, BBVX
Model BWVB
A
B
C
D
E
F
G
H J K L M N Filter Size
12
30 1/6
27 1/8
46
14
20
17 1/2
20
5 1/32 23 11 1/8 1 32 20 1/8 (1) 20x25x2

ModelBWVB& BXVB-08 thru 20 / BWVD & BXVD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.