Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
120 4 52 12000
6 52 12000
8 52 12000
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
391.3 300.5 83.0 2.9 0.677 1.6 2.7
528.7 365.1 110.8 4.9 1.058 2.1 3.6
617.7 407.0 129.1 7.9 1.436 2.5 4.2
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
265.9 265.9 57.3 1.4 0.508 1.1 1.9
387.4 313.0 82.1 3.5 0.976 1.6 2.7
459.1 342.3 97.0 4.6 1.348 1.9 3.2


BASIC VERTICAL - 4000 THRU 1200 CFM
Model BWVB
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
120
116 1/4
34 1/4
83
28
90
30
40
13 1/8 104 3/8 4 1/4 0 118 1/4 26 5/8 1 1/2 1 7/8 (8) 16x25x2
(2) 16x25x2

ModelBWHB& BXHB-40 thru 120 /BWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.