Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
40 4 20 4000
6 30 4000
8 30 4000
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
130.4 100.2 27.7 2.5 0.613 1.4 2.3
161.5 116.6 34.2 1.5 0.938 1.1 1.9
194.1 130.6 40.9 2.4 1.284 1.4 2.3
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
88.7 88.7 19.1 1.8 0.462 1.0 1.6
116.5 100.0 24.6 1.4 0.855 0.8 1.4
141.7 109.8 29.8 2.2 1.196 1.0 1.7


BASIC VERTICAL - 4000 THRU 12000 CFM
Model BWV
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
40
57 1/4
27 1/4
54
18
48
22 9/16
25 1/8
4 5/8 48 1/8 7 1/4 1 3/8 59 19 5/8 1 3/8 1 3/16 (2) 25x25x2

ModelBWHB& BXHB-40 thru 120 / DBHWBWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.