Cooling Capacities - All Horizontal & Vertical Units - EWT: 45°F & 50°F
 
SIZE ROWS CIR. CFM
50 4 20 5000
6 30 5000
8 30 5000
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
173.2 129.9 36.5 3.1 0.620 1.8 3.1
213.2 149.0 44.9 2.7 0.945 1.5 2.5
251.9 168.0 52.8 4.2 1.287 1.8 3.0
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
114.7 114.7 24.4 2.1 0.458 1.2 2.1
154.5 127.7 32.4 1.5 0.867 1.1 1.8
184.9 141.3 38.7 2.3 1.204 1.3 2.2


BASIC VERTICAL - 4000 THRU 12000 CFM
Model BWV
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
50
71 1/4
27 1/4
54
20
54
22 9/16
25 1/8
8 5/8 62 1/8 5 1/4 2 1/2 73 19 5/8 1 1/2 1 3/16 (4) 16x25x2

ModelBWHB& BXHB-40 thru 120 / DBHWBWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.