Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
60 4 20 6000
6 30 6000
8 30 6000
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
216.5 159.7 45.5 5.1 0.625 2.3 3.9
265.7 182.6 55.7 3.5 0.949 1.9 3.1
309.8 203.5 64.8 5.5 1.290 2.2 3.7
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
157.5 136.9 33.4 2.9 0.565 1.7 2.8
195.2 156.5 41.2 2.5 0.877 1.4 2.3
230.0 171.1 48.7 3.9 1.212 1.6 2.8


BASIC VERTICAL - 4000 THRU 12000 CFM
Model BWV
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
60
85 1/4
27 1/4
60
20
60
22 9/16
25 1/8
12 11/16 72 5/8 5 1/4 1 3/8 87 19 5/8 1 1/2 1 3/16 (3) 25x25x2

ModelBWHB& BXHB-40 thru 120 / DBHWBWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.