Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
80 4 26 8000
6 39 8000
8 52 8000
Entering Water Temperature 45°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
291.0 213.0 61.1 5.2 0.624 2.4 4.0
356.1 245.9 74.7 4.2 0.947 1.9 3.2
398.8 266.2 83.8 3.7 1.274 1.6 2.7
Entering Water Temperature 50°
TOTAL BTU SENS BTU GPM WPD APD GPM/CIR. TUBE VEL.
211.3 182.6 44.8 3.5 0.564 1.7 2.9
260.8 208.6 55.3 2.4 0.875 1.4 2.4
292.5 221.7 61.3 2.0 1.190 1.2 2.0


BASIC VERTICAL - 4000 THRU 12000 CFM
Model BWV
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
80
85 1/4
27 1/4
67
24
72
30 1/8
32 1/8
6 5/8 76 1/2 1 1/4 0 87 19 5/8 1 1/2 1 7/8 (8) 16x20x2

ModelBWHB& BXHB-40 thru 120 / BWHD & BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.