DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
8 4 3 800
6 7 800
8 7 800
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
32.8 22.7 54.1 53.8 0.641
36.4 24.9 51.5 51.5 0.962
44.1 28.9 47.0 47.0 1.282
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
28.2 20.9 56.1 55.9 0.641
30.7 23.0 53.8 53.8 0.937
38.1 26.1 50.2 50.2 1.274


DIMENSIONS - HORIZONTAL AIR HANDLER 800 THRU 2000 CFM
Model BXH
A
B
C
D
E
F
G
H J K L M N Filter Size
08
24 1/8
39 1/8
20 1/2
11 11/16
8 9/16
17 1/2
20
7 3/4 18 6 5/8 1 22 1/8 26 (1) 20x20x2

ModelBWHB& BXHB-08 thru 20 / DBHWBWHD &BXHD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.