DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
12 4 7 1200
6 7 1200
8 7 1200
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
42.2 30.6 56.7 55.9 0.692
59.0 39.1 50.2 50.2 1.037
69.5 44.2 46.3 46.3 1.383
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
35.1 28.2 58.5 58.0 0.674
50.7 36.0 52.6 52.6 1.037
60.6 40.7 49.0 49.0 1.383


DIMENSIONS - HORIZONTAL AIR HANDLER 800 THRU 2000 CFM
Model BXH
A
B
C
D
E
F
G
H J K L M N Filter Size
12
30 1/8
39 1/8
20 1/2
11 11/16
13 1/2
17 1/2
20
8 5/16 23 6 5/8 1 28 1/8 32 (1) 20x25x2

ModelBWHB& BXHB-08 thru 20 / DBHWBWHD &BXHD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.