DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
16 4 7 1600
6 7 1600
8 7 1600
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
63.6 44.2 54.7 54.3 0.641
84.1 55.5 48.3 48.3 0.962
96.2 61.2 45.0 45.0 1.282
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
54.3 40.7 56.7 56.4 0.641
73.3 50.1 51.4 51.4 0.962
85.2 56.4 47.8 47.8 1.282


DIMENSIONS - HORIZONTAL AIR HANDLER 800 THRU 2000 CFM
Model BXH
A
B
C
D
E
F
G
H J K L M N Filter Size
16
38 1/16
39 1/8
20 1/2
11 11/16
13 1/2
17 1/2
20
12 1/4 29 5/8 6 5/8 1 3/8 36 1/16 40 (1) 16x20x2

ModelBWHB& BXHB-08 thru 20 / DBHWBWHD &BXHD-08 thru 20 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.