DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
30 4 10 3000
6 15 3000
8 15 3000
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
124.6 85.0 54.1 53.8 0.641
154.0 102.0 48.9 48.9 0.993
178.3 114.7 45.0 45.0 1.324
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
107.7 78.3 56.1 55.7 0.662
133.4 93.9 51.4 51.4 0.993
157.4 103.7 48.4 48.4 1.324



ModelBWHB& BXHB-30 / BWHD & BXHD-30 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.