DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
40 4 20 4000
6 30 4000
8 30 4000
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
224.1 144.5 47.0 47.0 1.368
186.0 127.5 50.9 50.9 1.026
224.1 144.5 47.0 47.0 1.368
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
195.0 130.5 50.2 50.2 1.368
157.7 114.8 53.8 53.8 1.012
195.0 130.5 50.2 50.2 1.368


DIMENSIONS - HORIZONTAL AIR HANDLER 4000 THRU 12000 CFM
Model BXH
A
B
C
D
E
F
G
H J K L M N P Q R Filter Size
40
57 1/8
45 3/16
27 15/16
13 13/16
15 15/16
22 9/16
25 1/8
6 1/8 6 1/8 7 1/2 1 7/16 48 3/16 59 44 13/16 N/A 37 11/16 (2) 25x25x2

ModelBWHB& BXHB-40 thru 120 / DBHWBWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.