DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
80 4 26 8000
6 39 8000
8 52 8000
     
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
333.7 226.6 54.1 53.6 0.674
409.7 272.0 48.9 48.9 1.011
460.1 294.6 46.3 46.3 1.348
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
287.4 208.7 56.1 55.7 0.677
356.0 250.5 51.4 51.4 1.011
401.5 271.4 49.0 49.0 1.348


DIMENSIONS - HORIZONTAL AIR HANDLER 4000 THRU 12000 CFM
Model BXH
A
B
C
D
E
F
G
H J K L M N P Q R Filter Size
80
85 1/8
45 3/16
35 3/16
16 3/16
18 15/16
29 13/16
32 3/16
18 1/8 12 1/8 9 7/16 76 11/16 87 54 13/16 18 3/16 37 11/16 (8) 16x20x2

ModelBWHB& BXHB-40 thru 120 / DBHWBWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.