DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
120 4 52 12000
6 52 12000
8 52 12000
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
447.8 314.5 56.0 55.2 0.752
605.8 399.4 49.6 49.6 1.129
702.7 450.4 45.7 45.7 1.505
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
378.6 289.6 57.9 57.2 0.752
525.7 367.9 52.0 52.0 1.129
620.6 414.9 48.4 48.4 1.505


BASIC VERTICAL - 4000 THRU 12000 CFM
Model BXV
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
120
116 1/4
34 1/4
83
28
90
30
40
13 1/8 104 3/8 4 1/4 0 118 1/4 26 5/8 1 1/2 1 7/8 (8) 16x25x2
(2) 16x25x2

ModelBWHB& BXHB-40 thru 120 /BWHD &BXHD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.