DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
20 4 8 2000
6 16 2000
8 16 2000
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
76.9 53.8 55.4 54.8 0.737
88.4 62.3 51.5 51.5 1.105
108.7 70.8 47.6 47.6 1.474
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
65.3 49.6 57.3 56.8 0.737
74.2 54.8 54.9 54.9 1.074
92.8 65.2 50.2 50.2 1.463


DIMENSIONS - VERTICAL AIR HANDLER 800 THRU 3000 FOR MODELS BBVW, BBVX
Model BXV
A
B
C
D
E
F
G
H J K L M N Filter Size
20
38 1/16
27 1/8
54
18
24
17 1/2
20
7 1/16 29 5/8 7 1/8 1 3/8 40 20 1/8 (2) 16x20x2

ModelBWVB& BXVB-08 thru 30 / BWVD & BXVD-08 thru 30 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.