DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
 
SIZE ROWS CIR. CFM
60 4 20 6000
6 30 6000
8 30 6000
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
248.7 170.0 54.1 53.6 0.677
306.9 204.0 48.9 48.9 1.015
357.6 229.5 45.0 45.0 1.353
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
214.3 156.6 56.1 55.7 0.677
265.2 187.9 51.4 51.4 1.015
311.0 207.4 48.4 48.4 1.353


BASIC VERTICAL - 4000 THRU 12000 CFM
Model BXV
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
60
85 1/4
27 1/4
60
20
60
22 9/16
25 1/8
12 11/16 72 5/8 5 1/4 1 3/8 87 19 5/8 1 1/2 1 3/16 (3) 25x25x2

ModelBWVB& BXVB-40 thru 120 / BWVD &BXVD-40 thru 120 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.