Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
8 3 3 915
4 4 870
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
33.5 23.5 7.1 4.8 0.518 2.4 4.0
38.5 25.8 8.1 3.8 0.636 2.0 3.4
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
25.2 20.3 5.3 3.3 0.475 1.8 3.0
29.5 22.3 6.2 2.3 0.595 1.6 2.6


HORIZONTAL BASIC
Model DWHB
A
B
C
D
E
F
G
800
37 1/2
22 1/4
10 3/8
7 3/16
31
32 7/8
10 5/8

Model DWHB & DXHB-04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on DWHB & DXHB-04 & 06. 3/4" on DWHB & DXHB-08 - 12 and 1/2" HW on DWHB & DXHB-04 - 12.