Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
10 3 3 1080
4 4 1030
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
41.5 28.6 8.8 7.7 0.511 2.9 5.0
48.0 31.7 10.1 6.3 0.631 2.5 4.3
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
31.4 24.3 6.6 4.5 0.470 2.2 3.7
36.6 27.1 7.7 3.8 0.590 1.9 3.3


HORIZONTAL BASIC
Model DWHB
A
B
C
D
E
F
G
1000
49 1/2
22 1/4
10 3/8
7 3/16
37
38 7/8
10 5/8

Model DWHB & DXHB-04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on DWHB & DXHB-04 & 06. 3/4" on DWHB & DXHB-08 - 12 and 1/2" HW on DWHB & DXHB-04 - 12.