DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
3 3 1 320
4 1 300
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
14.9 10.0 51.5 51.5 0.185
16.4 10.4 48.3 48.3 0.222
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
13.1 9.2 53.8 53.8 0.185
14.6 9.8 50.2 50.2 0.222


Model DWHB-03 & DXHB-03

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on DWHB-03 / DXHB-03.