DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
6 3 2 660
4 3 630
6 3 575
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
24.1 16.8 56.7 55.5 0.407
27.1 18.3 53.4 53.1 0.505
32.5 21.2 46.3 46.3 0.658
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
20.7 15.5 58.5 57.3 0.407
23.2 16.8 55.5 55.3 0.505
28.8 19.1 49.6 49.6 0.658


HORIZONTAL BASIC
Model DXHB
A
B
C
D
E
F
G
600
37 1/2
21 3/4
9
6
31
32 7/8
9 1/2

Model DWHB & DXHB-04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on DWHB & DXHB-04 & 06. 3/4" on DWHB & DXHB-08 - 12 and 1/2" HW on DWHB & DXHB-04 - 12.