DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
8 3 3 915
4 4 870
6 6 795
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
29.0 21.4 58.6 57.1 0.532
33.9 24.0 54.7 54.6 0.656
39.6 26.5 49.6 49.6 0.856
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
24.5 19.1 60.9 58.8 0.532
28.8 21.6 57.3 56.7 0.656
33.7 23.9 52.6 52.6 0.856


HORIZONTAL BASIC
Model DXHB
A
B
C
D
E
F
G
800
37 1/2
22 1/4
10 3/8
7 3/16
31
32 7/8
10 5/8

Model DWHB & DXHB-04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on DWHB & DXHB-04 & 06. 3/4" on DWHB & DXHB-08 - 12 and 1/2" HW on DWHB & DXHB-04 - 12.