DX Cooling Capacities
- Entering Air 80° DB/67° WB
SIZE
ROWS
CIR.
CFM
10
3
3
1080
4
4
1030
6
6
945
Suction Temperature 42°F
TOTAL BTU
SENS BTU
LDB
LWB
APD
36.1
26.0
58.0
56.5
0.519
42.2
29.2
54.1
53.8
0.643
48.8
32.1
48.9
48.9
0.843
Suction Temperature 45°F
TOTAL BTU
SENS BTU
LDB
LWB
APD
30.8
24.0
59.7
58.2
0.519
36.1
26.9
56.1
56.0
0.643
42.2
29.6
51.4
51.4
0.843
HORIZONTAL BASIC
Model DXHB
A
B
C
D
E
F
G
1000
49 1/2
22 1/4
10 3/8
7 3/16
37
38 7/8
10 5/8
Model DWHB & DXHB-04 to 12
Right-hand unit shown, left hand unit opposite.
Coil connections determined by facing the supply-air opening.
Electrical junction box is located on the same side as the coil connections.
Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
Coil connections: 1/2" CW on DWHB & DXHB-04 & 06. 3/4" on DWHB & DXHB-08 - 12 and 1/2" HW on DWHB & DXHB-04 - 12.