DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
10 3 3 1080
4 4 1030
6 6 945
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
36.1 26.0 58.0 56.5 0.519
42.2 29.2 54.1 53.8 0.643
48.8 32.1 48.9 48.9 0.843
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
30.8 24.0 59.7 58.2 0.519
36.1 26.9 56.1 56.0 0.643
42.2 29.6 51.4 51.4 0.843


HORIZONTAL DELUXE
Model DXHD
A
B
C
D
E
F
G
H Filter Size
1000
12 3/8
61
28
25
58
12 3/8
7 3/4
36 1/4 (2) 12x25

Model DWHD& DXHD-04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on sizes 04 & 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 04-12.