Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
6 3 3 795
4 4 750
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
29.4 20.4 6.2 12.5 0.594 3.1 5.3
38.5 25.8 8.1 3.8 0.636 2.0 3.4
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
25.2 20.3 5.3 3.3 0.475 1.8 3.0
29.5 22.3 6.2 2.3 0.595 1.6 2.6


VERTICAL BASIC
Model WVBFT
A
B
C
D
E
F
G
Filter Size
600
20 5/32
14 5/32
57 5/8
10 15/32
8 15/32
2 7/32
3 1/32
16x20x1

Cased Vertical with Front Return / Top Supply Models 04 thru 08

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on sizes 04-08.