Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
8 3 3 1025
4 4 975
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
36.2 25.6 7.6 6.8 0.588 2.5 4.3
42.2 28.6 8.8 5.6 0.726 2.2 3.7
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
27.5 22.1 5.8 4.1 0.540 1.9 3.3
32.3 24.7 6.9 3.5 0.678 1.7 2.9


VERTICAL BASIC
Model WVBFT
A
B
C
D
E
F
G
Filter Size
800
20 5/32
14 5/32
57 5/8
10 15/32
9 13/32
2 7/32
3 1/32
20x20x1

Cased Vertical with Front Return / Top Supply Models 04 thru 08

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on sizes 04-08.