Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
12 3 3 1415
4 4 1350
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
53.3 36.9 11.3 7.7 0.529 2.8 4.8
65.1 42.5 13.7 14.9 0.663 3.4 5.8
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
40.2 31.4 8.5 4.8 0.486 2.1 3.6
50.1 36.4 10.5 9.5 0.622 2.6 4.4


VERTICAL BASIC
Model WVBFT
A
B
C
D
E
F
G
Filter Size
1200
20 11/32
20 5/16
57 5/8
10 3/8
11 15/16
2 1/8
3 1/16
20x20x1

Cased Vertical with Front Return / Top Supply Models 10 & 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 10 & 12) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on sizes 04-08.on 10; 3/4" on size 12; 1/2" HW on sizes 10 & 12.