Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
22 3 6 2075
4 8 2060
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD
86.5 60.2 17.5 17.3
99.4 65.7 18.9 13.6
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD
68.3 52.9 13.7 12.4
78.7 57.1 15.7 11.0


VERTICAL BASIC
Model WVBFT
A
B
C
D
E
F
G
Filter Size
1800
36
24 5/8
62 3/4
24
10 1/2
3
3
30x24x1

WVBFT & WVDFT - 10 thru 22

  • Right-hand unit shown, left-hand unit opposite.
  • Coil connections determined by facing the front access panel.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with a 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 10 & 12) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 10; 3/4" on size 12; 1/2" HW on sizes 10 & 12.