DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
8 3 3 780
4 4 755
6 6 710
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
27.9 19.9 56.7 55.7 0.376
32.3 21.9 53.4 53.1 0.477
37.6 24.6 48.3 48.3 0.650
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
23.7 18.3 58.5 57.6 0.376
27.6 20.2 55.5 55.4 0.477
32.3 22.2 51.4 51.4 0.650


VERTICAL BASIC
Model XVBBT
A
B
C
D
E
F
G
Filter Size
800
20 5/32
14 5/32
57 5/8
10 15/32
8 13/32
2 7/8
3 1/32
20x20x1

Models WVBBT, XVBBT, WVDBT, & XVDBT-04 thru 08

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on sizes 04-08.