DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
10 3 3 930
4 4 895
6 6 835
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
32.1 23.1 57.3 56.2 0.444
37.4 26.0 53.4 53.4 0.557
43.7 28.4 48.9 48.9 0.751
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
27.4 20.6 59.7 57.9 0.444
32.0 23.4 56.1 55.7 0.557
37.7 26.1 51.4 51.4 0.751


VERTICAL BASIC
Model WVBBT
A
B
C
D
E
F
G
Filter Size
1000
20 11/32
20 5/16
57 5/8
10 3/8
11 15/16
2 1/8
3 1/16
20x20x1

Models WVBBT, XVBBT, WVDBT, & XVDBT-10 & 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 10; 3/4" on size 12; 1/2" HW on sizes 10 & 12.