DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
12 3 3 1135
4 4 1075
6 6 980
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
35.4 25.7 59.3 57.3 0.604
41.7 29.7 54.7 54.6 0.741
48.9 32.6 49.6 49.6 0.962
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
30.3 23.7 60.9 58.9 0.604
35.6 26.6 57.3 56.7 0.741
42.1 29.4 52.6 52.6 0.962


VERTICAL BASIC
Model WVBBT
A
B
C
D
E
F
G
Filter Size
1200
20 11/32
20 5/16
57 5/8
10 3/8
11 15/16
2 1/8
3 1/16
20x20x1

Models WVBBT, XVBBT, WVDBT, & XVDBT-10 & 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 10; 3/4" on size 12; 1/2" HW on sizes 10 & 12.