DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
6 3 2 795
4 4 750
6 6 685
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
25.0 18.0 59.3 57.2 0.605
26.4 19.1 56.7 55.9 0.737
31.2 21.3 51.5 51.5 0.960
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
21.4 16.6 60.9 58.8 0.605
22.0 17.6 58.5 58.0 0.722
26.3 19.7 53.8 53.8 0.722


VERTICAL DELUXE
Model XVBFT
A
B
C
D
E
F
G
Filter Size
600
20 5/32
14 5/32
57 5/8
10 15/32
8 15/32
2 7/32
3 1/32
16x20x1

Cased Vertical with Front Return / Top Supply Models 04 thru 08

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on sizes 04-08.