DX Cooling Capacities- Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
8 3 3 1025
4 4 975
6 6 895
Suction Temperature 42°F
TOTAL BTU SENS BTU LDB LWB APD
31.3 22.5 59.9 57.5 0.608
36.8 26.2 55.4 55.0 0.750
43.6 29.2 50.2 50.2 0.985
Suction Temperature 45°F
TOTAL BTU SENS BTU LDB LWB APD
26.5 21.4 60.9 59.1 0.608
31.3 24.2 57.3 57.0 0.750
37.2 26.9 52.6 52.6 0.985


VERTICAL DELUXE
Model XVBFT
A
B
C
D
E
F
G
Filter Size
800
20 5/32
14 5/32
57 5/8
10 15/32
9 13/32
2 7/32
3 1/32
20x20x1

Cased Vertical with Front Return / Top Supply Models 04 thru 08

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 04-08) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on sizes 04-08.