Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
 
SIZE ROWS CIR. CFM
6 3 2 660
4 3 630
Entering Water Temperature 40°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
27.3 18.4 5.7 8.1 0.405 2.9 4.9
30.6 19.9 6.4 4.5 0.497 2.1 3.6
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
20.9 15.7 4.4 5.3 0.376 2.2 3.8
23.4 17.0 2.9 3.1 0.466 1.6 2.8


HORIZONTAL BASIC
Model DWHB
A
B
C
D
E
F
G
600
37 1/2
21 3/4
9
6
31
32 7/8
9 1/2

Model DWHB & DXHB-04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on DWHB & DXHB-04 & 06. 3/4" on DWHB & DXHB-08 - 12 and 1/2" HW on DWHB & DXHB-04 - 12.