USA Coil Products
Little Chill Coolers


STANDARD FEATURES

GENERAL
Little Chill Coolers
Provide Little Chill Cooler environmental control system. Unit to be self-contained, factory tested and charged. Unit con­figuration shall be horizontal, designed for ceiling mounting tem shall be provided with ETL label.

UNIT CABINETS
Little Chill Coolers
Cabinet and chassis shall be constructed of heavy gauge galvanized steel and designed for easy installation and ser­vice access. All service access to be through the sides of the unit without removing the unit from the ceiling. Cabinet shall be insulated with 1-1/2 lb. density insulation providing thermal and acoustical treatment. Mounting kit shall include vibration isolators.

AIR DISTRIBUTION SYSTEM
Little Chill Coolers
The air flow system shall include a direct drive double width, double inlet forward curved centrifugal fan arranged to draw air through the evaporator. The blower motor shall be mounted on vibration isolators and shall have three speeds to allow air flow to be adjusted to the specific requirements of the installation. The return/supply grille assembly shall include three-way outlet grille and a hinged return grille for filter access. Filter shall be 1” disposable type.

REFRIGERATION SYSTEM
Little Chill Coolers
The refrigeration system shall be self contained, and in­clude high-efficiency hermetic compressor designed for heat pump duty with vibration isolation.
The copper tube aluminum fin evaporator coil shall be mounted in a stainless steel drain pan. The drain pan shall be equipped with single float switch to stop unit operation in the event of a drain failure. The system shall include an externally equalized thermo­static expansion valve, liquid line filter, dryer sight glass with moisture indicator, manual reset high pressure, automatic reset low pressure switch and pressure fittings for charging, evacuation and service.

ELECTRICAL SYSTEM
Little Chill Coolers
The electrical box shall include all contactors, relays and transformers required for unit operation. The electrical box shall be located to allow full service from the side of the unit.

AIR COOLED CONDENSER
Little Chill Coolers
(Air Cooled System Only) The condenser coil shall be cop­per tube aluminum fin and factory mounted, piped and charged. The blower box assembly shall include a direct drive centrifugal fan for use with either plenum air or outside air via ductwork.

CHILLED WATER SYSTEMS
Little Chill Coolers
Chilled water systems shall include a copper tube aluminum fin cooling coil.


OPTIONAL FEATURES

ELECTRIC HEAT
Little Chill Coolers
The factory installed electric heat/reheat shall be low watt density type mounted downstream of the evaporator coil. Automatic reset safety switch plus a fusible link shall pro­vide for shutdown.

CONDENSATE PUMP
Little Chill Coolers
Provide low profile condensate pump capable of 30 gph @ 14’ of head suitable for mounting below the drain outlet and above the ceiling tiles including all traps, and associated piping. Pump to be U.L. listed and include built-in check valve and stainless steel motor shaft, and mounting brackets for attachment to unit.

THREE SPEED FAN SWITCH
Little Chill Coolers
Provide factory installed 3-speed fan switch to allow selec­tion of high - medium - low fan speed.

2-WAY OR 3-WAY CHILLED WATER VALVE
Little Chill Coolers
Provide 2/3-way solenoid valve to control water flow through the cooling coil. (Chilled water units only).

THERMOSTAT
Little Chill Coolers
Remote thermostat, wall mounted.
    Little Chill

OVERVIEW
Little Chill Coolers
NOMENCLATURE
Little Chill Coolers
STANDARD &
OPTIONAL FEATURES

Little Chill Coolers
PERFORMANCE SPECS
- Air Cooled

Little Chill Coolers
Little Chill Coolers
PERFORMANCE SPECS
- DX/Water

Little Chill Coolers
DIMENSIONS
- Air Cooled

Little Chill Coolers
Little Chill Coolers
DIMENSIONS
- Chilled Water - Direct Expansion

Little Chill Coolers
Print Product Literature